Online UPS PowerWalker VFI 6000T LCD (L) PowerWalker VFI 10000T LCD (L) Manual (EN) Uninterruptible Power Supply System
7 Outstanding adaptability to the worst mains input condition. Extra wide input voltage, frequency range and waveform, avoid excessive diss
8Wave form sinusoidal Load type PF 0.5~1, lagging THDV < 2% @ full linear load <5% @ full non linear load Overload In Line mode**: 10 min
93.4 Typical Backup Time (Typical values at 25°C in minutes) Model No. 100 % Load PowerWalker VFI 6000T LCD 5 PowerWalker VFI 10000T LCD 4 3.5
114. Installation 4.1 Moving to The Installation Site The series UPS has wheels making it easy to move the UPS to the installation site after
122. Check all packaging materials to ensure that no items are missing. The shipping package contains: ● A UPS ● A user manual ● A USB cable
134.3.2 Installation Use cable cross section and protective device specification Model PowerWalker VFI 6000T LCD (L) PowerWalker VFI 10000T LCD
14 Fig.4-6 Typical external isolating device installation 2) No matter the UPS is connected to the mains power or not, the output of the UPS may be
158) Connect other input and output wires to the corresponding input and output terminals according to the following diagram. 9) It is requested t
1614) If it is necessary to connect the inductance load such as a monitor or a laser printer to the UPS, the start-up power should be use
CONTENT: 1. Safety and EMC Instructions ... 1 1.1 Installation ...
173) Set the external battery pack breaker in “OFF” position and connect the 20 pieces of batteries in series. 4) Connect the external battery
185. Operation 5.1 Display Panel The UPS has a four-button dot matrix LCD with dual color backlight. Standard back-light is used to light up the d
19 Enter main menu When displaying default UPS status summary screen, press this button for >1s to enter the main menu tree Exit m
20Note:::: ●: Lightened constantly : #1-#4 Lightened circularly : Flashing ↑: Depended on the fault/warning status or
21Input220 V60 HzOutput220 V60 Hz5400 W273.0 V100%Utility input informationUPS output informationLoad informationBattery informationUPS operating st
225.2.2 Battery mode The example of LCD display in battery mode is shown in the following diagram. Fig. 5-4 Battery mode When the UPS
235.2.4 Bypass without output The LCD display in bypass mode without output is shown in the following diagram. Fig. 5-6 Bypass mode without ou
242) It is attention that the transfer time of UPS output from HE mode to battery mode is about 10ms. But it is still too long for some
25 Fig. 5-9 Warning 5.2.8 Fault When the fault occurs, it illustrates that some fatal problems happened, the UPS would directly cut off th
26 Fig. 5-11 Overload While doing the battery test, LEDs would be lighted circularly, and the symbol of battery test would be shown on the display.
7.3 Trouble Shooting In Else Cases ... 50 8. Battery Maintenance ...
275.3 Turning On and Turning Off UPS Attention: The UPS could only be turning on while connecting with the mains at the first time. Attention: Ple
285.3.3 Turning off UPS with mains 1) To turn off the inverter of UPS by pressing button continuously for more than 3s and the buzzer wi
29 Fig. 5-14 Main menu tree WELCOMEAlarm # 41Battery Volt: 220VBattery chargingCharger level:100%Status:Para
305.4.2 The UPS status menu By pressing on the menu of “UPS status”, the display would enter the next UPS status menu tree. The content
315.4.3 The event log menu By pressing on the menu of “Event log”, the display would enter the next event menu tree. All the old event, alarm
325.4.4 The measurement menu By pressing on the menu of “Measurement”, the display would enter the next measurement menu tree. A lot of detailed
335.4.5 The control menu By pressing on the menu of “Control”, the display would enter the next control menu tree. 1) Single UPS turn off: is on
34 Fig. 5-18 Control menu tree
35Example: clear EPO status Clear EPO statusBy press <1sStatus:EPO activeClear:noStatus:EPO activeClear:yesBy press or &
36 Fig. 5-20 Identification menu tree 5.4.7 The setting menu Please contact your local distributor for further information before using the settings
11. Safety and EMC Instructions Please read carefully the following user manual and the safety instructions before installing the unit or using t
37 Fig. 5-21 Setting menu tree By press on the menu of “Identification”, the display would enter the next setti
38Table 5-4 Submenu item Optional Values Default value User password enabled/disabled disabled Audio alarm enabled/disabled enabled Rated outp
39Example: set rated output voltage value Fig. 5-22 Set rated output voltage value
406. Special Function The series UPS has some special functions, which could satisfy some special application of user. And the funct
416.2 Converter Function 6.2.1 Brief introduction of Converter function In converter mode, the UPS would free run with fixed output freque
426.3.2 Parallel installation and operation How to install a new parallel UPS system: 1) Before installing a new parallel UPS system, user
43IP_G IP_N IP_L B+ B- B_G J1 J2 OP_N OP_L OP_GIP_G IP_N IP_L B+ B- B_G J1
44 Fig. 6-2 Parallel System Installation Diagram 10) Do not switch on the output breaker of each UPS, switch on the input breaker of the each UPS,
4513) Press the button of one UPS, each UPS would start to turn on, after turning on, the UPSs should work parallel in the Line mode. How to joi
46automatically, set the own maintenance switch of each UPS from “UPS” to “BPS”. 3) Set the main maintenance switch or static switch fro
2 With the installation of the equipment, the sum of the leakage current of the UPS and the connected load does not exceed 5% of rated value of in
477. Trouble Shooting If the UPS system does not operate correctly, first check the operating information on the LCD display. Please attempt to
48Over Charge Battery is over charged The UPS will turn off the charger until the battery voltage is normal Model Pin Error UPS internal fault
497.2 Trouble Shooting According To Fault Indication Problem Displayed Possible cause Remedy Inv Overload Fault Overload Check the loads and
507.3 Trouble Shooting In Else Cases Problem Possible cause Remedy No indication, no warning tone even though system is connected to mains power s
518. Battery Maintenance Battery replacement should be performed by qualified personnel. This series UPS only requires minimal maintenance
529. Communication Port 9.1 USB Interface The USB port is compliance with USB 1.1 protocol for its communication software. 9.2 Dry contact Interfa
53RS-232 communication port pin assignments Pin Signal name Function Direction from the UPS 1 Unused Not applicable 2 Tx Transmit to external
5410. Software Installation WinPower is UPS monitoring software, featuring user-friendly interface to monitor and control your UPS. This unique soft
3 Before carrying out any kind of service and/or maintenance, isolate UPS and disconnect the batteries. Verify that no current is present
41.6 Standards * Safety IEC/EN 62040-1 * EMI Conducted Emission...:IEC/EN 62040-2 Category C3 Radiated Emission...
52. Description of Commonly Used Symbols Some or all of the following symbols may be used in this manual. It is advisable to familiarize yourself
63. Introduction This On-Line series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection s